Industrial monitoring projects typically grow in scale and complexity. A project that starts with ”we need to monitor the temperature of a cooling system” ends up including pressure monitoring, flow measurement, voltage monitoring, and perhaps pulse counting from existing meters — all at the same locations, with the same radio coverage requirements and the same app integration.
A traditional dedicated-logger solution then requires 4-6 different radio platforms from different manufacturers, with separate base stations, apps, configurations and batteries. Configuration complexity grows with the square of the number of device types.
T&D’s solution: one common radio platform (RTR505B) with INTERCHANGEABLE INPUT MODULES. The same radio housing, the same base station, the same app, the same battery standard. Only the input module is swapped depending on the sensor type.
Five available input modules
1. 56-PTM-3010 (Pt100/Pt1000 module):
- Supports both Pt100 (100 Ω at 0 °C) and Pt1000 (1000 Ω at 0 °C).
- 3-wire or 4-wire Kelvin connection.
- Measurement range: -199 to +600 °C.
- Accuracy: ±0.1 °C in the mid-range.
- Applications: precision measurement on bearings, motor windings, cooling systems, lab environments.
2. 56-TCM-3010 (Thermocouple module):
- Supports types K, J, T, S.
- Measurement range: -199 to +1760 °C depending on type.
- Internal cold-junction compensation.
- Applications: furnaces, annealing processes, exhaust gas measurement, calibration labs.
3. 56-VIM-3010 (Voltage module):
- Measurement range: 0-22 V DC.
- Resolution: 0.1 mV.
- Warm-up function (for powering active sensors).
- Scale conversion: define your own unit (e.g. bar, pH, %RH) via linear mapping.
- Applications: solar panel strings, output from pressure sensors, conductivity meters, gas sensors.
4. 56-AIM-3010 (Current loop module):
- Measurement range: 4-20 mA (operational up to 40 mA for overcurrent detection).
- Scale conversion to any unit.
- Applications: industrial process instrumentation (pressure transmitters, level meters, flow meters with 4-20 mA output).
5. 56-PIC-3150 (Pulse counter cable):
- Counts 0-61,439 pulses per logging interval.
- Accepts contact closure (reed relay) or voltage pulse (5-24 V).
- Scale conversion: define pulses per unit (e.g. 1 pulse per liter → l/min directly).
- Applications: water meters, gas meters, energy meters, production counters.
Economic analysis — platform vs dedicated
Take a monitoring project with 15 measurement points across 5 different types:
- 5 units temperature (Pt100).
- 3 units thermocouple (K type, furnace temperature).
- 3 units voltage (solar panel monitoring).
- 2 units current (4-20 mA from pressure sensors).
- 2 units pulse (water meters).
Dedicated-logger approach:
- 5 Pt100 loggers: 5 × 1,600 = 8,000 SEK.
- 3 TC loggers: 3 × 1,800 = 5,400 SEK.
- 3 voltage loggers: 3 × 1,700 = 5,100 SEK.
- 2 current loggers: 2 × 1,900 = 3,800 SEK.
- 2 pulse loggers: 2 × 1,400 = 2,800 SEK.
- Total loggers: 25,100 SEK
- Plus 3-4 base stations (if different series): 3 × 5,000 = 15,000 SEK.
- Plus separate app integration.
- Grand total: ~40,000 SEK
Modular platform (RTR505B):
- 15 RTR505B loggers: 15 × 1,629 = 24,435 SEK.
- Input modules: 5 Pt + 3 TC + 3 V + 2 A + 2 Pulse = 15 modules × ~800-1,200 SEK = ~15,000 SEK.
- 1 base station (the same for all): 5,000 SEK.
- 1 common app.
- Grand total: ~44,000 SEK
At the time of purchase, the platform appears SLIGHTLY more expensive, but the payoff comes later:
- Replacement after a sensor failure: only the module costs (~800 SEK), not a whole logger (1,600-2,000 SEK).
- Rebalancing between types: move modules between loggers without buying new loggers.
- Quick project adaptation: a new measurement need means buying a module, not a new logger plus base station.
- Simpler inventory: one logger type in stock instead of 5.
Radio range of 150 m line of sight
869.7-870 MHz is the EU ISM band (Industrial, Scientific, Medical) with licence-free use. T&D’s radio uses LoRa-like modulation for long range and low power consumption.
Ranges:
- Line of sight (outdoors): 150 m.
- Office environment (suspended ceilings, interior walls): 40-80 m.
- Industrial environment (metal walls, machine interference): 20-50 m.
- Through a concrete wall (25 cm): 10-30 m.
For longer distances, the RTR505B can be used in a ”repeater chain”: the loggers act as mesh nodes and relay the signal to the base station. The range can thereby be extended to 500+ meters with proper placement.
10 months of battery life
Single-band radio plus low-power electronics gives 10 months of operation on one LS14250 lithium cell (half-AA, 1200 mAh, 3.6 V).
Consumption: 2-5 mA for 100 ms per measurement + 5-10 μA in sleep.
At a 60-second measurement interval: 15 mAh per month → 800 months of theoretical battery life → in practice 10 months, limited by battery self-discharge and radio collisions.
At a 1-second interval: 900 mAh per month → 1.3 months of battery life. Notably shorter — fast intervals are for specific investigation periods, not continuous operation.
16,000 data points — Endless mode
Standard logging mode: when the memory is full, the logger STOPS. Good for fixed batch logging.
Endless mode: when the memory is full, the logger starts OVERWRITING the oldest data. Good for continuous monitoring where losing historical data points is acceptable.
Calculations for different intervals (Endless mode shows the historical range):
- 1 sec interval: 4.4 hours of history.
- 60 sec interval: 11 days of history.
- 10 min interval: 111 days of history.
- 60 min interval: 666 days of history.
In practice: the RTR500B base station empties the loggers at set intervals (typically daily) and transfers the data to a central server. This means the local memory only needs to hold a buffer of ~24 hours.
Bluetooth 4.2 BLE for configuration
Bluetooth is NOT used for daily measurement data (the 869 MHz radio to the RTR500B base station is used for that). Bluetooth is used for INITIAL CONFIGURATION and FIELD DIAGNOSTICS:
- Configure the logging interval.
- Set up scale conversion for voltage/current/pulse modules.
- Change the radio channel if interference occurs.
- Verify battery level and latest measured value in the field.
- Download memory contents directly if the base station is unavailable.
Configuration is done via the T&D Thermo app on iOS/Android (the same app as other T&D Bluetooth loggers).
Applications
Power plant monitoring: Combined temperature (bearings, motor windings), voltage (generator output), and pulse (rotational speed from encoders) on the same radio platform.
Solar power plant: String voltage monitoring + panel temperature + current loop from inverters.
Waterworks infrastructure: Pulse counting from flow meters + pressure monitoring via 4-20 mA transmitters + cooling water temperature.
Foundry and smelter monitoring: Furnace temperature (type S thermocouple for high temperatures) + cooling water (Pt100) + gas flow meters (pulse).
Building management: HVAC temperature (Pt100) + differential pressure (4-20 mA from transmitters) + energy meter pulse counting.
Scientific research: Multi-parameter environmental monitoring where different sensor types must be synchronized.
Clinical pharmacy: Cold chain verification for medicines (Pt100 precision) + differential pressure in cleanrooms (4-20 mA) + particle counter pulse (if applicable).
Specifications
- Platform: modular wireless logger.
- Input module: sold separately (5 variants available).
- Measurement channels: 1 (via the selected module).
- Radio: 869.7-870 MHz (EU ISM band).
- Range: ~150 m line of sight.
- Memory: 16,000 data points with Endless mode.
- Logging interval: 15 fixed values from 1 sec to 60 min.
- Battery life: ~10 months on LS14250.
- Display: LCD with current value and low-battery warning.
- Configuration: Bluetooth 4.2 BLE via mobile app.
What you get for your money
T&D RTR505B wireless multifunction logger, modular platform with interchangeable input modules (Pt100/Pt1000, thermocouple K/J/T/S, voltage 0-22V, current loop 4-20 mA, pulse counter — all sold separately), 869.7-870 MHz radio with 150 m range, 16,000 data point memory with Endless mode, 15 logging intervals (1 sec – 60 min), ~10 months of battery life on an LS14250 lithium cell, LCD display, Bluetooth 4.2 BLE for configuration via the T&D Thermo app. 1,629 SEK per logger (input module sold separately).
The standard platform for industrial monitoring projects that scale across several sensor types — power plants, solar power plants, waterworks, foundries, HVAC. The price premium over dedicated single-purpose loggers is justified when the project involves more than 2-3 sensor types, or when flexibility for future reconfiguration is valuable.