Hoppa till innehåll
Free shipping on orders over 3000 SEK excl. VAT! Volume discount: 5 pcs 2% · 10 pcs 3% · 25 pcs 5%
Volume discount: 5 pcs 2% · 10 pcs 3% · 25 pcs 5%The air in the fridge doesn’t show the temperature of the vaccineThe Air in the Fridge Lies: How to Monitor the Real Temperature of Your Goods Without False AlarmsHow to show in seconds whether the load stayed at the right temperature and humidity during transportThe air feels heavy long before anyone measures it: how to make carbon dioxide levels visibleThe freezer showed -18 °C on Monday morning, but what happened over the weekend?The core temperature is what counts, and it only shows if someone has logged itTwo measuring points and the difference between them: how to make the temperature differential in a process visibleFour Measuring Points and a Time-Stamped Log Show Where the Heat in the Process Actually GoesYou Can’t Guess the Core Temperature of a Product: How to Document It Without Standing Next to ItThe fridge looked like it was holding the right temperature, but what happened overnight?Volume discount: 5 pcs 2% · 10 pcs 3% · 25 pcs 5%The air in the fridge doesn’t show the temperature of the vaccineThe Air in the Fridge Lies: How to Monitor the Real Temperature of Your Goods Without False AlarmsHow to show in seconds whether the load stayed at the right temperature and humidity during transportThe air feels heavy long before anyone measures it: how to make carbon dioxide levels visibleThe freezer showed -18 °C on Monday morning, but what happened over the weekend?The core temperature is what counts, and it only shows if someone has logged itTwo measuring points and the difference between them: how to make the temperature differential in a process visibleFour Measuring Points and a Time-Stamped Log Show Where the Heat in the Process Actually GoesYou Can’t Guess the Core Temperature of a Product: How to Document It Without Standing Next to ItThe fridge looked like it was holding the right temperature, but what happened overnight?

TandD TR-55I-P Pulse Counter Logger: When the Water Flow Meter Outputs 1 Pulse per Liter and Scale Conversion Displays l/min Directly, No Excel Formulas Needed

Published 12 July 2026 at 22:34

A property manager wants to document a building’s water consumption per hour over a 2-week period in order to identify leaks. The existing water meter has a PULSE OUTPUT: a digital pulse each time 1 liter passes through the meter. Without a pulse counter, this signal is useless.

The TandD TR-55I-P connects directly to the water meter’s pulse output using two wires. The logger counts pulses and stores the total every 15 minutes. Over 2 weeks that comes to 1,344 data points (well below the 16,000 memory limit). When collecting the data, the logger is connected optically to a USB reader. Result: a PDF graph of the building’s water consumption in 15-minute intervals.

If the graph shows constant consumption even between 03:00 and 05:00 when everyone is asleep, there is probably a leak. If consumption is zero at that time, there are no leaks.

Pulse outputs: standard in electricity, gas and water metering

Many modern commercial meters have a PULSE OUTPUT as a standard feature. Each pulse represents a known VOLUME or ENERGY quantity:

  • Electricity meters: 1 pulse per 1, 10 or 100 Wh (varies by manufacturer).
  • Water meters: 1 pulse per 1, 10 or 100 liters.
  • Gas meters: 1 pulse per 0.1 or 0.01 m³.
  • Flow meters: 1 pulse per defined quantity (varies by model).
  • Tachometers: 1 pulse per revolution (turbine, motor, refrigeration compressor).

The pulse is typically a SHORT CONTACT CLOSURE (10-100 ms long) from a reed relay or open-collector output. No complex data protocol is needed. The TR-55I-P can handle either a CONTACT input (potential-free) or a VOLTAGE SIGNAL (e.g. 5-24 V DC pulses).

Scale conversion: elegance from the user’s perspective

The logger can be configured with a CONVERSION COEFFICIENT that converts pulses into the user’s preferred unit directly when the data is read. A concrete example:

Without scale conversion: The report shows ”247 pulses on 3 March 2026 at 14:00”. The user has to calculate manually: 247 pulses × 10 Wh/pulse = 2,470 Wh = 2.47 kWh, either with an Excel formula or by hand.

With scale conversion (coefficient 10): The report directly shows ”2.47 kWh on 3 March 2026 at 14:00”. No conversion needed.

The benefit grows when several loggers are used at the same time with different meter types. One logger measures electricity (coefficient 10 Wh/pulse), another water (1 l/pulse), and a third gas (0.1 m³/pulse). Without scale conversion, the operator has to remember each coefficient. With scale conversion, each logger directly displays its own physical quantity.

16,000 data points

At different logging intervals:

  • 1 minute: 11 days.
  • 5 minutes: 55 days.
  • 15 minutes: 166 days (5.5 months).
  • 30 minutes: 333 days (11 months).
  • 1 hour: 666 days (almost 2 years).

For typical energy monitoring (15-minute to 1-hour intervals), the memory lasts for many months. Data can therefore be collected quarterly or semi-annually instead of every week.

Pulse counting range: 0-61,439 per interval

The logger counts up to 61,439 pulses between data-storage timestamps. In which scenarios is this not enough?

  • A large industrial electricity meter with 1 pulse per 1 Wh: 61,439 Wh = 61.4 kWh per interval.
  • At a 15-minute interval = 61.4 kWh / 0.25 h = 245 kW instantaneous power. Reasonable for a medium-sized industrial facility, too high for a residential or commercial building.
  • At a 1-hour interval = 61 kW instantaneous power. Sufficient for most applications.

For extremely high pulse frequencies (above 61 kHz on the fastest meters), the operator may need to shorten the interval or use meters with a lower pulse-per-unit coefficient.

TandD TR-55I-P kompakt pulsräkningslogger

Optical data transfer

The TR-55I-P uses OPTICAL COMMUNICATION to read out data, not USB and not Bluetooth. The reader (TandD 56-TR-50U2) has a window surface that is placed against the corresponding window on the logger. Data is transferred as flashing sequences of infrared light.

Why optical communication? There are two reasons:

  • Electrical isolation: No electrical contact between the logger and the computer. This protects against ESD damage and electrical short circuits.
  • Outdoor installation: The logger can be permanently installed in a waterproof enclosure. Optical communication only requires a small window.

Drawback: it requires a READER (TR-50U2), which is sold separately (~2,000 SEK). One reader can be used with an unlimited number of loggers, so the investment is a one-time cost.

4-year battery life

The lithium battery (LS14250) provides approximately 4 years of continuous operation, depending on the logging interval and pulse frequency. This is dramatically longer than most data logger batteries (typically 1-2 years).

Practical consequence: a logger installed today can be left untouched for 4 years, collecting data continuously and read out periodically with the optical reader. Replacing the battery requires opening the logger’s housing (which may compromise the IP protection), so plan for a replacement every 4 years.

Compact physical size

The logger measures 62 × 47 × 19 mm, about the thickness of a credit card. It fits:

  • Next to the meters in the electrical cabinet.
  • In a water meter chamber with IP-rated sealing.
  • On the motor housing for speed measurement.
  • In a pocket for mobile measurement during field service.

Applications

Building energy monitoring: Electricity, water and gas per apartment or per zone as a basis for cost allocation.

Industrial production monitoring: Electricity consumption per machine and production per hour.

Leak detection (water): Nighttime consumption identifies hidden leaks.

Solar panel inverter output: Many inverters have a pulse output, making it simple to log energy production.

Motor and pump operating time: 1 pulse per revolution = total number of revolutions over time = lifespan planning.

Dosing system verification: Chemical dosing in waterworks and washing facilities.

Rainfall measurement: Tipping-bucket rain gauges (0.2 mm of rain per tip) are a classic pulse counting application.

Bicycle and hiking trails (counters): Passage counting for traffic analysis.

What you get for your money

TandD TR-55I-P compact pulse counting logger, 1 channel pulse counting 0-61,439 pulses per interval, contact or voltage input, built-in scale conversion for direct display in the user’s unit (l/min, kWh, m³, rpm, dosing units), 16,000 data points of internal memory, 15 fixed logging intervals, alarm LED, ~4 years of battery life on an LS14250 lithium battery, optical communication via the TR-50U2 reader (sold separately), compact 62 × 47 × 19 mm size. 1,758 SEK (excluding sensor and reader).

The standard tool for property managers, energy technicians, industrial maintenance, HVAC service and other businesses that need to monitor pulse outputs from existing meters. It combines simple installation (two wires) with long battery life and flexible scale conversion. For 4-20 mA signals or multi-channel applications, corresponding TandD models are available.

Read more: TandD TR-55I-P pulse counting logger in the shop →