Hoppa till innehåll
Free shipping on orders over 3000 SEK excl. VAT! Volume discount: 5 pcs 2% · 10 pcs 3% · 25 pcs 5%
Volume discount: 5 pcs 2% · 10 pcs 3% · 25 pcs 5%The furnace drifted overnight, but no one noticed until the batch was ruinedThe air in the fridge doesn’t show the temperature of the vaccineThe Air in the Fridge Lies: How to Monitor the Real Temperature of Your Goods Without False AlarmsHow to show in seconds whether the load stayed at the right temperature and humidity during transportThe air feels heavy long before anyone measures it: how to make carbon dioxide levels visibleThe freezer showed -18 °C on Monday morning, but what happened over the weekend?The core temperature is what counts, and it only shows if someone has logged itTwo measuring points and the difference between them: how to make the temperature differential in a process visibleFour Measuring Points and a Time-Stamped Log Show Where the Heat in the Process Actually GoesYou Can’t Guess the Core Temperature of a Product: How to Document It Without Standing Next to ItVolume discount: 5 pcs 2% · 10 pcs 3% · 25 pcs 5%The furnace drifted overnight, but no one noticed until the batch was ruinedThe air in the fridge doesn’t show the temperature of the vaccineThe Air in the Fridge Lies: How to Monitor the Real Temperature of Your Goods Without False AlarmsHow to show in seconds whether the load stayed at the right temperature and humidity during transportThe air feels heavy long before anyone measures it: how to make carbon dioxide levels visibleThe freezer showed -18 °C on Monday morning, but what happened over the weekend?The core temperature is what counts, and it only shows if someone has logged itTwo measuring points and the difference between them: how to make the temperature differential in a process visibleFour Measuring Points and a Time-Stamped Log Show Where the Heat in the Process Actually GoesYou Can’t Guess the Core Temperature of a Product: How to Document It Without Standing Next to It

Extech SDL350 Hot-Wire Anemometer with SD Logger: Why the Experienced HVAC Technician Carries Two Anemometers and When the Telescopic Probe Fits Into a 215 cm Duct

Published July 9, 2026 at 02:11

On the tool cart of an experienced HVAC technician, as a rule, sit two anemometers. That’s not overkill — it’s experience. The vane anemometer’s large head for open-duct measurement and rough balancing. The hot-wire probe’s thin metal filament in the telescoping sensor for tight openings and low speed. The two are complementary tools that measure the same physical quantity — airflow — but in different mechanical regimes. The Extech SDL350 is the hot-wire model that fills that second slot.

The hot-wire principle — heat loss as a proxy for velocity

The hot-wire anemometer has a thin metal wire (typically platinum or nickel alloy, 5-20 µm diameter) electrically heated to a fixed 200-250 °C above ambient air temperature. As air flows across the wire, it cools — and the electrical power needed to maintain the temperature difference is proportional to air velocity according to King’s law:

P = (A + B × √v) × ΔT

Where P is electrical power, v is velocity, ΔT is the temperature difference, and A and B are calibration constants. The square-root form is physical and means the sensor is MOST sensitive at low velocities — exactly where the impeller anemometer is weakest.

Practical consequence: 0-30 m/s measurement range with high sensitivity at the low end

An impeller anemometer has a minimum measurable velocity of about 0.3-0.5 m/s (ball-bearing friction prevents rotation below that). At this minimum, accuracy is also at its worst. A hot-wire anemometer can measure down to 0.05 m/s (100 times lower) with better accuracy there.

This makes hot-wire the first choice for:

  • Supply air in bedrooms, offices, and residential environments (typically 0.1-0.5 m/s at the diffuser).
  • Cleanroom airflow verification (typically 0.3-0.5 m/s beneath HEPA filters).
  • Natural convection from heat sources (0.05-0.2 m/s).
  • Draft through leaky windows (identifying where the leak is).

The telescoping probe — 215 cm when you need to measure deep inside

A real-world scenario from an HVAC technician: a 200×400 mm supply duct, cast into the concrete slab. The accessible opening is 20 cm above the ceiling, 2 meters above the floor. The impeller anemometer with its 60 mm sensor head doesn’t fit in the opening and can’t reach further in. The hot-wire probe’s thin tip (6 mm diameter on the Extech model) fits. The telescoping rod extends to 215 cm so the operator can reach into the duct and measure 1 meter in from the opening.

The telescoping probe also has another practical advantage: it can be positioned at ONE measurement point while the operator stands at another. This is critical when the measurement point is on a ceiling or under a machine where the operator’s hand can’t fit.

Extech SDL350 hot-wire-anemometer med teleskopsond och SD-logger

SD-card logging + NIST certificate = regulatory usefulness

A NIST calibration certificate makes measurement data legally significant. When commissioning cleanroom ventilation in pharmaceutical production (GMP documentation), hospital operating rooms (class 5 cleanroom requirements), or electronics manufacturing, legally significant documentation is required. The Extech SDL350 with NIST certification meets this directly.

SD-card logging (up to 20 million readings on a 2 GB card) allows continuous documentation during commissioning. An 8-hour equilibration measurement of a supply duct produces ~3,000 readings at 10-second sampling — easy to process in Excel after the job.

K/J thermocouple input for high-temperature measurement

The instrument’s K/J thermocouple input is for measuring air temperature in extreme environments (e.g. flue gas ducts at 200-500 °C, industrial furnace supply). The hot-wire sensor itself cannot measure at these temperatures — the Teflon insulation that holds the wire fixed in place doesn’t survive the heat. The thermocouple complements it with high-temperature capability.

Where impeller vs. hot-wire actually compete

Above 3-5 m/s, both technologies are roughly equivalent in accuracy. In that range, you choose based on physical access:

  • Open duct, large opening: Impeller. More rugged, more resistant to dust and small particles.
  • Tight opening, remote point: Hot-wire with telescoping probe. The only one that fits.
  • Turbulent zone: Hot-wire. Faster response (~0.1 s vs ~1 s for the impeller) captures velocity fluctuations.
  • Outdoor wind measurement: Impeller. Hot-wire is more sensitive to particles and rain.

Physical limits of hot-wire

The instrument has practical limitations the operator needs to know:

  • Direction-sensitive: The hot-wire measures the component of velocity PERPENDICULAR to the wire. If the airflow is parallel to the wire, almost no reading is registered. The probe must be oriented perpendicular to the expected flow direction.
  • Dust and small particles: Can stick to the wire and thermally insulate it, causing erroneous readings. The probe should be cleaned regularly (carefully — the wire is extremely fragile).
  • Condensing environments: Water droplets on the wire cool it drastically, giving false readings. In condensing air (bathrooms, drying rooms), hot-wire is unsuitable.
  • Electromagnetic interference: Near powerful electrical equipment, microampere-level signal interference can affect the reading.

What you get for the money

Extech SDL350 thermo-anemometer with hot-wire sensor and telescoping probe (extends up to 215 cm), K/J thermocouple input, air velocity measurement range 0.4-30 m/s, air temperature measurement, SD-card logging (20 million readings on a 2 GB card), NIST calibration certificate (5-week lead time), 99 manual memory locations, MIN/MAX memory, data hold, auto power-off, PC interface, 6× AA batteries, hard carrying case.

12,057 SEK is the instrument cost. Combined with the impeller-based SDL310 (~6,800 SEK), the total cost for both anemometers comes to ~19,000 SEK — and the HVAC technician has complementary tools for every measurement scenario, from cleanroom verification to ventilation rough balancing.